← All products
GREE · Gree water-cooled systems

Gree DL Series Water-cooled Packaged Unit

ADDED FROM GREE DOCUMENTSSource-checked summary
Original product image from the Gree catalogue, PDF page 1.
Product summary

Water-cooled industrial packaged units for direct or ducted air supply. 32–196 kW cooling-capacity range, with R410A refrigerant.

RefrigerantR410APDF page 1 ↗
Cooling-capacity range32–196 kWPDF page 1 ↗
Power supply — first 7-model table380-400 3N~50HzPDF page 2 ↗
Discuss your project ↗View / download Gree document ↗

Specifications from the Gree document

RefrigerantR410APDF page 1 ↗
Cooling-capacity range32–196 kWPDF page 1 ↗
Power supply — first 7-model table380-400 3N~50HzPDF page 2 ↗
Power supply — last 3-model table380-400/3/50PDF page 2 ↗
Control-temperature range16~30±2 °CPDF page 2 ↗
Condenser — typeTube bundlePDF page 2 ↗
Indoor fan — type and driveCentrifugal; belt-drivenPDF page 2 ↗
FilterNylon mesh filterPDF page 2 ↗
Drain pipeG3/4PDF page 2 ↗
PDF row: “Tổng công suất làm lạnh” (retained, not interpreted)First 7 models: 8.0, 12.0, 16.2, 19.4, 24.3, 28.2, 31.6 kW; last 3: 35.5, 39.0, 48.4 kWPDF page 2 ↗

10 models in the DL catalogue

PDF page 2 ↗

ModelCooling (kW)Airflow (m³/h)ESP (Pa)Condenser water (m³/h)Weight (kg)
L32S/NaE-M325500756.9429
L49S/NaE-M4980007510.6540
L65S/NaE-M(P)651080010014680
L80S/NaE-M801400010017.2800
L98S/NaE-M981600011521.1870
L116S/NaE-M1161900014025950
L130S/NaE-M13022000140281110
L145S/NaE-M1452300014031.21120
L160S/NaE-M1602600019034.41130
L196S/NaE-M1963200025042.11445
01Product overview

The unit is designed to supply air directly or through ducts to regulate indoor temperature. The document describes it as having a compact structure and high energy-use efficiency.

PDF page 1 ↗
02Key features

Page 1 lists these features: energy saving, easier maintenance, compact design, comprehensive protection, high ESP, and remote monitoring.

PDF page 1 ↗
03Refrigerant and control

The cover displays the R410A refrigerant marking and identifies the Z3D3003J control panel.

PDF page 1 ↗
04Specification-table data

The page-2 specification tables list 10 models: 7 in the upper table and 3 in the lower table. Cooling capacity is listed from 32 to 196 kW, and airflow from 5,500 to 32,000 m³/h.

PDF page 2 ↗
05Operating range

The operating-range table lists cooling water at 18–42 °C; evaporator-coil entering-air dry-bulb temperature at 15–35 °C; and wet-bulb temperature at 13–24 °C. In cooling mode, evaporator entering air is 27 °C dry bulb and 19 °C wet bulb, while condenser entering water is 30±0.3 °C.

PDF page 2 ↗

Specification notes

The PDF reproduces a row labeled “Tổng công suất làm lạnh” with values 8.0, 12.0, 16.2, 19.4, 24.3, 28.2, 31.6 kW for the first 7 models and 35.5, 39.0, 48.4 kW for the last 3 models. This label is ambiguous/may be mistranslated and may refer to power input, but the PDF does not confirm that interpretation; the values are therefore retained in a separate source-row entry and are not used to populate coolingKw or relabeled as power input. Page 1 lists L105S/NaE-M among the models/images, but page 2 provides no specification row for L105S, so it is omitted from models.

For L116S/NaE-M, both HRT and the PDF list 116 kW capacity, 19,000 m³/h airflow and 140 Pa ESP. However, HRT lists 380–415 V/380 V, 50/60 Hz, while the PDF lists 380–400 V, 50 Hz. This website uses PDF values in the table and does not merge the sources. HRT writes 28.2KW/h for power consumption; that unit is not used as a confirmed specification. Warranty, pricing and availability require quotation-time confirmation.